The following refer to sheet metal auxiliary gutters.
Auxiliary gutters examples.
Figuring the 20 is easy for example.
Nonmetallic auxiliary gutters shall be per mitted to be installed outdoors where listed and.
The capacities of bars cannot exceed 1 55 a per square millimeter 1000 a per square inch for copper and 1 09 a per mm2 700 a per square inch for aluminum.
A similar change occurred in article 366 for auxiliary gutters.
Auxiliary gutters shall not contain more than 30 conductors at any cross section unless the additional conductors are for signal 01 control circuits.
Code quiz of day.
I get a lot of calls to make sure that the gutter that they are using is up to code.
This auxiliary gutter used as a pull box is 5ft long 14inches deep by 14inches in height.
Ampacity of conductors in auxiliary gutters.
Sizing a gutter for the proper fit is relatively easy.
There are two 4inch conduits feeding the bottom of the gutter with 4x600mcm conductors in parallel in each which pass straight through to the two 4inch nipples which connect to the bottom of the meter assembly feeding the 800 amp breaker.
Now when determining gutter or wireway fill the sum of the cross sectional areas of all contained conductors and cables at any cross section shall not exceed 20 percent of the interior cross sectional area of the wireway.
The sum of the cross sectional areas of all contained conductors at any cross section of an auxiliary gutter shall not exceed 20 of the interior cross sectional area of the gutter.
Of its interior cross sectional area 366 22 a b this is for both sheet metal and nonmetallic gutters.
When there are not more than 30 current carrying conductors the derating factors for ampacities do not have to be applied.
Article 366 covers the use installation and construction requirements of auxiliary gutters and associated fittings.
This article covers the use installation and construction requirements of metal auxiliary gutters and nonmetallic auxiliary gutters and associated fittings.